SIRIUS SOFT STARTER, S0, 12.5A, 7.5KW/500V, 40 DEGR., AC 400-600V, AC/DC 24V, SCREW TERMINALS, THERMISTOR MOTOR PROTECTION

Артикул: 3RW4024-1TB05
Наименование: SIRIUS SOFT STARTER, S0, 12.5A, 7.5KW/500V, 40 DEGR., AC 400-600V, AC/DC 24V, SCREW TERMINALS, THERMISTOR MOTOR PROTECTION (siemens)
Производитель: Siemens


Наименование продукта
SIRIUS SOFT STARTER, S0, 12.5A, 7.5KW/500V, 40 DEGR., AC 400-600V, AC/DC 24V, SCREW TERMINALS, THERMISTOR MOTOR PROTECTION
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2007-07-02
Manuals weitere>>
3RW4024-1TB05"> Справочник по аппарату плавного пуска SIRIUS 3RW30 / 3RW40  2012-03-14
SIRIUS SOFT STARTER, S0, 12.5A, 7.5KW/500V, 40 DEGR., AC 400-600V, AC/DC 24V, SCREW TERMINALS, THERMISTOR MOTOR PROTECTION
 
General details:
product brand name   SIRIUS
Product equipment    
  • integrated bridging contact system
  Yes
  • thyristors
  Yes
Product function    
  • intrinsic device protection
  Yes
  • motor overload protection
  Yes
  • evaluation of thermal resistor motor protection
  Yes
  • reset external
  Yes
  • adjustable current limitation
  Yes
  • inside-delta circuit
  No
Product component / outlet for enine brake   No
Item designation    
  • according to DIN EN 61346-2
  Q
  • according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
  G
 
Power Electronics:
product designation   soft starters for standard applications
Operating current    
  • at 40 °C / rated value
A 12.5
  • at 50 °C / rated value
A 11
  • at 60 °C / rated value
A 10
Emitted mechanical power / for three-phase servomotors    
  • at 400 V / at standard switching / at 40 °C
   
  • rated value
W 5,500
  • at 500 V / at standard switching / at 40 °C
   
  • rated value
W 7,500
Operating frequency    
  • rated value
Hz 50 60
Relative negative tolerance / of the operating frequency % -10
Relative positive tolerance / of the operating frequency % 10
Operating voltage / with standard circuit / rated value V 400 600
Relative negative tolerance / of the operating voltage / with standard circuit % -15
Relative positive tolerance / of the operating voltage / with standard circuit % 10
Minimum load in % of l_M % 20
Adjustable rated current / of the motor / for motor overload protection / minimum A 5
Continuous operating current in % of l_e / at 40°C % 115
Active power loss / at operating current / at 40°C / during operating phase / typical W 2
 
Control electronics:
Type of voltage / of the controlled supply voltage   AC/DC
Control supply voltage frequency / 1 / rated value Hz 50
Control supply voltage frequency / 2 / rated value Hz 60
Relative negative tolerance / of the control supply voltage frequency % -10
Relative positive tolerance / of the control supply voltage frequency % 10
Control supply voltage / 1    
  • at 50 Hz / for AC
V 24
  • at 60 Hz / for AC
V 24
Relative negative tolerance / of the control supply voltage / at 60 Hz / for AC % -20
Relative positive tolerance / of the control supply voltage / at 60 Hz / for AC % 20
Control supply voltage / 1 / for DC / rated value V 24
Relative negative tolerance / of the control supply voltage / for DC % -20
Relative positive tolerance / of the control supply voltage / for DC % 20
Type of display / for fault signal   red
 
Mechanical design:
Size of the engine control device   S0
Width mm 45
Height mm 125
Depth mm 155
Type of mounting   screw and snap-on mounting
Built in orientation   With additional fan: With vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back Without additional fan: With vertical mounting surface +/-10° rotatable, with vertical mounting surface +/- 10° t
Distance, to be maintained, to the ranks assembly    
  • upwards
mm 60
  • sidewards
mm 15
  • downwards
mm 40
Altitude of installation site / at a height over sea level m 5,000
Cable length / maximum m 300
Number of poles / for main current circuit   3
 
Electrical connections:
Design of the electrical connection    
  • for main current circuit
  screw-type terminals
  • for auxiliary and control current circuit
  screw-type terminals
Number of NC contacts / for auxiliary contacts   0
Number of NO contacts / for auxiliary contacts   2
Number of change-over switches / for auxiliary contacts   1
Type of the connectable conductor cross-section / for main contacts / for box terminal / when using the front clamping point    
  • solid
  2x (1.5 ... 2.5 mm²), 2x (2.5 ... 6 mm²), max. 1x 10 mm²
  • finely stranded / with conductor end processing
  2x (1.5 ... 2.5 mm²), 2x (2.5 ... 6 mm²)
Type of the connectable conductor cross-section / for AWG conductors / for main contacts / for box terminal    
  • when using the front c lamping point
  1x 8, 2x (16 ... 10)
Type of the connectable conductor cross-section    
  • for auxiliary contacts

Назад в раздел