SIRIUS SOFT STARTER, S12, 205 A, 200 HP/575 V, 50 DEG., 400-600 V AC, 115 V AC, CAGE CLAMP TERMINALS

Артикул: 3RW4073-2BB35
Наименование: SIRIUS SOFT STARTER, S12, 205 A, 200 HP/575 V, 50 DEG., 400-600 V AC, 115 V AC, CAGE CLAMP TERMINALS (siemens)
Производитель: Siemens


Наименование продукта
SIRIUS SOFT STARTER, S12, 205 A, 200 HP/575 V, 50 DEG., 400-600 V AC, 115 V AC, CAGE CLAMP TERMINALS
Жизненный цикл продукта
Разрешение на поставку Постепенное снятие продукта с производства Снятие продукта с производства Окончательное снятие продукта с производства
2004-11-22
Manuals weitere>>
3RW4073-2BB35"> Справочник по аппарату плавного пуска SIRIUS 3RW30 / 3RW40  2012-03-14
SIRIUS SOFT STARTER, S12, 205 A, 200 HP/575 V, 50 DEG., 400-600 V AC, 115 V AC, CAGE CLAMP TERMINALS
 
General details:
product brand name   SIRIUS
Product equipment    
  • integrated bridging contact system
  Yes
  • thyristors
  Yes
Product function    
  • intrinsic device protection
  Yes
  • motor overload protection
  Yes
  • evaluation of thermal resistor motor protection
  No
  • reset external
  Yes
  • adjustable current limitation
  Yes
  • inside-delta circuit
  No
Product component / outlet for enine brake   No
Item designation    
  • according to DIN EN 61346-2
  Q
  • according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
  G
 
Power Electronics:
product designation   soft starters for standard applications
Operating current    
  • at 40 °C / rated value
A 230
  • at 50 °C / rated value
A 205
  • at 60 °C / rated value
A 180
Emitted mechanical power / for three-phase servomotors    
  • at 400 V / at standard switching / at 40 °C
   
  • rated value
W 132,000
  • at 500 V / at standard switching / at 40 °C
   
  • rated value
W 160,000
Operating frequency    
  • rated value
Hz 50 60
Relative negative tolerance / of the operating frequency % -10
Relative positive tolerance / of the operating frequency % 10
Operating voltage / with standard circuit / rated value V 400 600
Relative negative tolerance / of the operating voltage / with standard circuit % -15
Relative positive tolerance / of the operating voltage / with standard circuit % 10
Minimum load in % of l_M % 20
Adjustable rated current / of the motor / for motor overload protection / minimum A 130
Continuous operating current in % of l_e / at 40°C % 115
Active power loss / at operating current / at 40°C / during operating phase / typical W 90
 
Control electronics:
Type of voltage / of the controlled supply voltage   AC
Control supply voltage frequency / 1 / rated value Hz 50
Control supply voltage frequency / 2 / rated value Hz 60
Relative negative tolerance / of the control supply voltage frequency % -10
Relative positive tolerance / of the control supply voltage frequency % 10
Control supply voltage / 1    
  • at 50 Hz / for AC
V 115
  • at 60 Hz / for AC
V 115
Relative negative tolerance / of the control supply voltage / at 60 Hz / for AC % -15
Relative positive tolerance / of the control supply voltage / at 60 Hz / for AC % 10
Type of display / for fault signal   red
 
Mechanical design:
Size of the engine control device   S12
Width mm 160
Height mm 230
Depth mm 278
Type of mounting   screw fixing
Built in orientation   With additional fan: With vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back Without additional fan: With vertical mounting surface +/-10° rotatable, with vertical mounting surface +/- 10° t
Distance, to be maintained, to the ranks assembly    
  • upwards
mm 100
  • sidewards
mm 5
  • downwards
mm 75
Altitude of installation site / at a height over sea level m 5,000
Cable length / maximum m 300
Number of poles / for main current circuit   3
 
Electrical connections:
Design of the electrical connection    
  • for main current circuit
  busbar connection
  • for auxiliary and control current circuit
  spring-loaded terminals
Number of NC contacts / for auxiliary contacts   0
Number of NO contacts / for auxiliary contacts   2
Number of change-over switches / for auxiliary contacts   1
Type of the connectable conductor cross-section / for main contacts / for box terminal / when using the front clamping point    
  • finely stranded / with conductor end processing
  70 ... 240 mm²
  • finely stranded / without conductor end processing
  70 ... 240 mm²
  • stranded
  95 ... 300 mm²
Type of the connectable conductor cross-section / for main contacts / for box terminal / when using the back clamping point    
  • finely stranded / with conductor end processing
  120 ... 185 mm²
  • without conductor final cutting / without conductor end processing
  120 ... 185 mm²
  • stranded
  120 ... 240 mm²

Назад в раздел