| SIRIUS SOFT STARTER, VALUES AT 575V, 50DEGREES, STANDARD: 1051A, 1200HP, INSIDE DELTA: 1820A, 2050HP, AC 400-600V, AC 115V, SCREW TERMINALS |
|
General details: |
product brand name | | SIRIUS |
Product equipment | | |
- integrated bridging contact system
| | Yes |
| | Yes |
Product function | | |
- intrinsic device protection
| | Yes |
- motor overload protection
| | Yes |
- evaluation of thermal resistor motor protection
| | Yes |
| | Yes |
- adjustable current limitation
| | Yes |
| | Yes |
Product component / outlet for enine brake | | Yes |
Item designation | | |
- according to DIN EN 61346-2
| | Q |
- according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
| | G |
|
Power Electronics: |
product designation | | soft starters for high feature applications |
Operating current | | |
| A | 1,214 |
| A | 1,076 |
| A | 970 |
- for three-phase servomotors / at 3-phase root switching
| | |
| A | 2,103 |
| A | 1,864 |
| A | 1,680 |
Emitted mechanical power / for three-phase servomotors | | |
- at 400 V / at standard switching / at 40 °C
| | |
| W | 710,000 |
- at 500 V / at standard switching / at 40 °C
| | |
| W | 900,000 |
- at 400 V / at 3-phase root switching / at 40 °C
| | |
| W | 1,200,000 |
- at 500 V / at 3-phase root switching / at 40 °C
| | |
| W | 1,500,000 |
Operating frequency | | |
| Hz | 50… 60 |
Relative negative tolerance / of the operating frequency | % | -10 |
Relative positive tolerance / of the operating frequency | % | 10 |
Operating voltage / with standard circuit / rated value | V | 400… 600 |
Relative negative tolerance / of the operating voltage / with standard circuit | % | -15 |
Relative positive tolerance / of the operating voltage / with standard circuit | % | 10 |
Operating voltage / at 3-phase root switching / rated value | V | 400… 600 |
Relative negative tolerance / of the operating voltage / with inside-delta circuit | % | -15 |
Relative positive tolerance / of the operating voltage / with inside-delta circuit | % | 10 |
Minimum load in % of l_M | % | 8 |
Adjustable rated current / of the motor / for motor overload protection / minimum | A | 242 |
Continuous operating current in % of l_e / at 40°C | % | 115 |
Active power loss / at operating current / at 40°C / during operating phase / typical | W | 630 |
|
Control electronics: |
Type of voltage / of the controlled supply voltage | | AC |
Control supply voltage frequency / 1 / rated value | Hz | 50 |
Control supply voltage frequency / 2 / rated value | Hz | 60 |
Relative negative tolerance / of the control supply voltage frequency | % | -10 |
Relative positive tolerance / of the control supply voltage frequency | % | 10 |
Control supply voltage / 1 | | |
| V | 115 |
| V | 115 |
Relative negative tolerance / of the control supply voltage / at 60 Hz / for AC | % | -15 |
Relative positive tolerance / of the control supply voltage / at 60 Hz / for AC | % | 10 |
Type of display / for fault signal | | Display |
|
Mechanical design: |
Width | mm | 575 |
Height | mm | 780 |
Depth | mm | 292 |
Type of mounting | | screw fixing |
Built in orientation | | bei senkrechter Montageebene +/-90° drehbar, bei senkrechter Montageebene +/- 22,5° nach vorne und hinten kippbar |
Distance, to be maintained, to the ranks assembly | | |
| mm | 100 |
| mm | 5 |
| mm | 75 |
Altitude of installation site / at a height over sea level | m | 5,000 |
Cable length / maximum | m | 500 |
Number of poles / for main current circuit | | 3 |
|
Electrical connections: |
Design of the electrical connection | | |
| | busbar connection |
- for auxiliary and control current circuit
| | screw-type terminals |
Number of NC contacts / for auxiliary contacts | | 0 |
Number of NO contacts / for auxiliary contacts | | Back to the section
|