| FAIL-SAFE DIGITAL MODULE DM-F PROFISAFE; FOR FAIL-SAFE SWITCH-OFF VIA BUS / PROFISAFE; UV: 24 V DC, 2 RELAY ENABLING CIRCUITS; 2 RELAY OUTPUTS; 3 OUTPUTS; MAX. ERR. SIL (IEC 61508): 3; MAX. ERR. PL (ISO 13849-1): E; |
|
General technical data: |
product brand name | | SIRIUS |
Item designation / according to DIN EN 61346-2 | | F |
Item designation / according to DIN 40719 extendable after IEC 204-2 / according to IEC 750 | | F |
|
Installation/mounting/dimensions: |
Built in orientation | | any |
Type of mounting | | screw and snap-on mounting |
Width | mm | 45 |
Height | mm | 106 |
Depth | mm | 124 |
|
Connections: |
Design of the electrical connection / for auxiliary and control current circuit | | screw-type terminals |
Conductor cross-section that can be connected / for auxiliary contact | | |
| mm² | 0.5… 4 |
| | |
- with conductor end processing
| mm² | 0.5… 2.5 |
|
Ambient conditions: |
Ambient temperature | | |
| °C | -25… +60 |
| °C | -40… +80 |
| °C | -40… +80 |
Relative humidity | | |
| % | 5… 95 |
Installation altitude / at a height over sea level / maximum | m | 2,000 |
Protection class IP | | IP20 |
Resistance against vibration | | 1-6 Hz / 15 mm; 6-500 Hz / 2 g |
EMC immunity to interference / according to IEC 60947-1 | | corresponds to degree of severity 3 |
Conductor-bound parasitic coupling BURST | | |
- according to IEC 61000-4-4
| | 2 kV network connection / 1 kV control connection |
Conductor-bound parasitic coupling conductor-earth SURGE | | |
- according to IEC 61000-4-5
| | 1 kV |
Conductor-bound parasitic coupling conductor-conductor SURGE | | |
- according to IEC 61000-4-5
| | 0.5 kV |
Field-bound parasitic coupling | | |
- according to IEC 61000-4-3
| | 10 V/m |
EMC emitted interference / according to IEC 60947-1 | | class A |
Insulation voltage / rated value | V | 300 |
Impulse voltage resistance / rated value | V | 4,000 |
|
Safety: |
safety Integrated Level / according to IEC 61508 | | SIL3 |
Performance level (PL) / according to ISO 13849-1 | | e |
Category / according to EN 954-1 | | 4 |
Category / according to ISO 13849-1 | | 4 |
Product function | | |
| | No |
| | No |
| | No |
| | No |
- protective door monitoring
| | No |
- magnetic switch monitoring Normally closed contact-Normally open contact
| | No |
| | No |
- magnetic switch monitoring Normally closed contact-Normally closed contact
| | No |
| | No |
Acceptability for application | | |
- EMERGENCY-OFF circuit monitoring
| | No |
| | No |
- position switch monitoring
| | No |
| | No |
- magnetically operated switches monitoring
| | No |
- proximity switches monitoring
| | No |
- tactile sensor monitoring
| | No |
- opto-electronical protection device monitoring
| | No |
| | No |
Product feature / transverse contact-secure | | Yes |
Design of the input / reducing-entrance | | Yes |
Probability of dangerous failure per hour (PFHD) / with high demand rate / according to EN 62061 | 1/h | 0.43599999999999994E-8 |
Average probability of failure on demand (PFDavg) / with low demand rate / according to IEC 61508 | 1/y | 0.513E-5 |
SIL claim limit (for a subsystem) / according to EN 62061 | | 3 |
T1 value / for proof test interval or service life / according to IEC 61508 | a | 20 |
PROFIsafe monitoring time F_WD_Time | ms | 250 |
Response time / in faultless state WCDT | ms | 150 |
Response time / in case of failure OFDT | ms | 200 |
Backslide delay time / at mains power cut / typical | ms | 40 |
Backslide delay time / at mains power cut / maximum | ms | 80 |
Recovery time / after mains power cut / typical | s | 1 |
|
Communication: |
Protocol / will be supported / PROFIsafe protocol | | Yes |
|
Inputs/ Outputs: |
Number of inputs | | 4 |
Number of digital inputs | | 3 |
Number of analog inputs | | 0 |
Number of outputs | | 2 |
Number of outputs / as contact-affected switching element | | 2 |
Switching behaviour | | monostable |
Number of analog outputs | | Назад в раздел
|