General features | |
Processor | Intel Pentium 4 technology; Intel Celeron 2.0 GHz, Intel Pentium 4 2.8 GHz, Intel Pentium 4 mobile 2.2 GHz |
Memory type | DDR |
Main memory | 256 MB to 2 GB |
Free slots | 2x PCI, 2x PCI/ISA shared, 1x ISA (slots with board retainer) |
Operating system | Windows 2000 Prof. (Multi Language), Windows XP Prof. (Multi Language), opt. without operating system |
Additional info on operating system | Multi Language: DE, EN, IT, FR, SP, KOR, CHN (Traditional), CHN (Simplified), JPN |
SIMATIC Software | Optionally in package with SIMATIC WinCC or WinCC flexible |
Drives | |
Diskette drive | 1.4 MB, on rear, can be operated from side |
Optical drives | optional: DVD-ROM or DVD±R±RW combi-drive; on rear, can be operated from side |
Hard disk/Mass storage | 3.5" EIDE hard disk drive e 40 GB, optional: 3.5" hard disk drive e 80 GB, optional: 2x 2.5" hard disk module e 40 GB, optional 2x 2.5" SATA-RAID1 hard disk module e 60GB. All drives with vibration- and oscillation-resistant mountings. |
interfaces | |
Graphics interface | DVI-I usable for additional display unit (VGA via adapter); color depth 16 bit, video memory up to 32MB, resolution in each case as integrated display |
Connection for keyboard/mouse | PS/2 or USB / PS/2 or USB |
Parallel interface | LPT1 (EPP/ECP) |
serial interface | COM1: 1x V.24 (RS-232), COM2: 1x V.24 (RS-232C) |
PROFIBUS/MPI | onboard, isolated, max. 12 Mbit/s, no plug-in card necessary, CP5611-compatible |
USB | 1x at front, 2x at rear, USB 2.0 (500mA) |
Ethernet | onboard, 1 x 10/100 Mbit, RJ45, no plugin card necessary |
Multimedia | no |
Supply voltage | |
Supply voltage | 110V / 230V AC (autorange) 50/60 Hz; optional 24V DC (only with Pentium 4 mobile processor) |
Monitoring functions | |
Temperature | Yes |
Watchdog | Yes |
Status LEDs | Power, temperature (on front panel) |
Degree of protection | |
Front to EN 60529 | IP65 (on front) to EN60529 and NEMA4 |
Ambient conditions | |
Vibration load in operation | Tested to DIN IEC 68-2-6: 10 to 58 Hz: 0.075 mm, 58 to 200 Hz: 9.8 m/s2 (1 g) |
Shock loading in operation | Tested to DIN IEC 68-2-29: 50 m/s2 (5g), 30 ms, 100 shocks |
Relative humidity | Tested to DIN IEC 68-2-3, DIN IEC 68-2-30, DIN IEC 68-2-56: 5% to 80% at 25 °C (no condensation) |
Ambient temperature in operation | In full configuration: +5°C to +45°C or +5°C to +50°C in installation space, if at front max. 40°C (only with Pentium 4 Mobile 2.2 GHz) |
Certifications & Standards | |
Approval | CE, cULus (508) |
EMC | CE, EN 55011, EN 61000-6-4, EN 61000-6-2 |
| |