Protection degree IP65 and IP69k Outwit-proof according to ISO 13850/EN 418 2-channel, compelled connected TГњV-approval for system components is available
Datasheet as PDF in following languages:
Technical Data: VAA-2E-F85-V1 Product Description AS-Interface emergency off button General specifications Slave type Standard slave Functional safety related parameters MTTFd 200 a B10d 1 E+5 Electrical specifications Rated operating voltage 26.5 ... 31.6 V from AS-Interface Rated operating current ≤ 20 mA Protection class III Input Number/Type 2 NC Safety function by positive opening in accordance with IEC/EN 60947-5-1 Reset by pulling Supply from AS-Interface Programming instructions Profile S-7.B.E IO code 7 ID code B ID1 code 0 ID2 code E Data bits (function via AS-Interface) input output D0 dyn. safety code 1 -D1 dyn. safety code 1 -D2 dyn. safety code 2 -D3 dyn. safety code 2 -Parameter bits (programmable via AS-i)function P0 not used P1 not used P2 not used P3 not used Ambient conditions Ambient temperature -25 ... 55 В°C (-13 ... 131 В°F) Storage temperature -25 ... 85 В°C (-13 ... 185 В°F) Mechanical specifications Protection degree IP65 in accordance with EN 60529 and IP69k Connection M12 round connector