Not available for purchase, If you need assistance please contact us sales@quad-industry.com Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@quad-industry.com
Cabinet module 4 inputs (sensor for alternating voltage) and 4 relay outputs
General specifications
Slave type
Standard slave
UL File Number
E87056
Indicators/operating means
LED PWR/FAULT
dual-LED green/red green: AS-Interface voltage, normal operation red: communication error or address 0
LED IN
switching state (input); 4 LED yellow
LED OUT
Switching state (output); 4 LED yellow
Electrical specifications
Rated operating voltage
26.5 ... 31.6 V from AS-Interface
Rated operating current
≤ 100 mA
Input
Number/Type
4 sensors, V AC
Supply
external 110 V AC
Switching point
0 (unattenuated)
≤ 2 mA
1 (attenuated)
≥ 20 mA
Output
Number/Type
4 relay outputs
Electrical isolation
AS-Interface - Outputs: Safe isolation according to EN 50178 (250 V AC) Output - Output: Safe isolation according to EN 50178 (250 V AC)
Contact loading
2 A/30 V DC per output 2 A/250 V AC per output
Life span
mechanical: 30 x 106 switching cycles electrical: 1 x 106 operations (30 V DC, 2 A, ohmic) 5 x 106 operations (250 V AC, 2 A, cosφ = 1) 4.5 x 106 switching cycles (250 V AC, 2 A, cosφ = 0.7)
Programming instructions
Profile
S-7.F
IO code
7
ID code
F
Data bits (function via AS-Interface)
inputoutput
D0
IN1OUT1
D1
IN2OUT2
D2
IN3OUT3
D3
IN4OUT4
Parameter bits (programmable via AS-i)
function
P0
communication monitoring P0 = 1 (basic setting), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition