AS-Interface sensor/actuator module | VAA-4EA-KF2-ZE/T

Артикул: VAA-4EA-KF2-ZE/T
Наименование: AS-Interface sensor/actuator module | VAA-4EA-KF2-ZE/T
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@quad-industry.com
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@quad-industry.com

  • Housing with removable, coded terminals
  • AS-Interface connection via Power Rail
  • Communication monitoring, turn-off
  • 115/230 V AC electronic outputs
  • Inputs for 2- and 3-wire sensors
  • Addressing jack
  • Power supply of outputs from the external auxiliary voltage
  • Power supply of inputs from the module
  • Function display for bus, inputs and outputs

Datasheet as PDF in following languages:


Technical Data: VAA-4EA-KF2-ZE/T

Product Description
Cabinet module
4 inputs (PNP) and 4 electronic outputs
General specifications
Slave typeStandard slave
AS-Interface specificationV2.0
Required master specification≥ V2.0
UL File NumberE87056
Indicators/operating means
LED PWR/FAULTdual LED green/red
green: AS-Interface voltage
red: communication error or address 0
green/red flashing: overload sensor supply
LED INswitching state (input); 4 LED yellow
LED OUTSwitching state (output); 4 LED yellow
Electrical specifications
Auxiliary voltage (output)115 / 230 V AC ± 10 %
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 80 mA (without sensors) / max. 230 mA
Input
Number/Type4 inputs for 2- or 3-wire sensors (PNP), DC
Supplyfrom AS-Interface
Voltage21 ... 31 V DC
Current loading capacity≤ 150 mA, short-circuit protected
Switching point
0 (unattenuated)≤ 2 mA
1 (attenuated)≥ 4 mA
Output
Number/Type4 electronic outputs, AC
Supplyfrom external auxiliary voltage UAUX
Current≤ 2 A total (TB ≤ 50В°C)
≤ 1.5 A total (TB ≤ 60В°C)
≤ 0.7 A total (TB ≤ 70В°C)
Voltage≥ (UAUX - 2 V)
Electrical isolationAS-Interface/Outputs: Safe isolation according to EN 50178 (250 V AC)
Programming instructions
ProfileS-7.F
IO code7
ID codeF
Data bits (function via AS-Interface) input output
D0 IN1 OUT1
D1 IN2 OUT2
D2 IN3 OUT3
D3 IN4 OUT4
Parameter bits (programmable via AS-i)function
P0communication monitoring
P0 = 1 (basic setting), monitoring = ON, i.e. if communication fails, the outputs are de-energised
P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition
P1not used
P2not used
P3not used
Compliance with standards and directives
Standard conformity
Protection degreeEN 60529
Ambient conditions
Ambient temperature-25 ... 70 В°C (-13 ... 158 В°F)
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Mechanical specifications
Protection degreeIP20
Connectionremovable coded terminals, Power Rail
Mass170 g
MountingDIN mounting rail


Назад в раздел