AS-Interface sensor/actuator module | VBA-2E2A-G2-ZA0/EA0

Артикул: VBA-2E2A-G2-ZA0/EA0
Наименование: AS-Interface sensor/actuator module | VBA-2E2A-G2-ZA0/EA0
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@quad-industry.com
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@quad-industry.com

  • AS-Interface certificate
  • Protection degree IP67
  • A/B slave with extended addressing possibility for up to 62 slaves
  • Addressing jack
  • Flat cable connection with cable piercing technique, variable flat cable guide
  • Communication monitoring
  • Inputs for 2-, 3-, and 4-wire sensors
  • Power supply of outputs from the external auxiliary voltage
  • Supply for inputs from AS-Interface
  • Ground connection (FE) possible
  • Function display for bus, ext. auxiliary voltage, inputs and outputs
  • Detection of overload on sensor supply
  • Detection of output overload

Datasheet as PDF in following languages:


Technical Data: VBA-2E2A-G2-ZA0/EA0

Product Description
G2 flat module
2 inputs (NPN) and 2 electronic outputs
General specifications
Slave typeA/B slave
Indicators/operating means
LED FAULTerror display; LED red
red: communication error or address is 0
red flashing: overload of sensor power supply or outputs
LED PWRAS-Interface voltage; LED green
LED AUXext. auxiliary voltage UAUX ; LED green
LED INswitching state (input); 2 LED yellow
LED OUTSwitching state (output); 2 LED yellow
Electrical specifications
Auxiliary voltage (output)20 ... 30 V DC PELV
(protection class 3 according to VDE 0106/IEC 364-4-41)
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 40 mA (without sensors) / max. 140 mA
Protection classIII
Input
Number/Type2 inputs for 2- or 3-wire sensors (NPN), DC
alternative 1 input for 4-wire sensor (NPN), DC
Supplyfrom AS-Interface
Voltage21 ... 31 V
Current loading capacity≤ 100 mA (TB ≤ 40 В°C),
≤ 75 mA (TB ≤ 60 В°C), overload-proof and short-circuit protected
Input current≤ 8 mA (limited internally)
Switching pointaccording to DIN EN 61131-2 (Type 2)
0 (unattenuated)≤ 2 mA
1 (attenuated)≥ 4 mA
Output
Number/Type2 Electronic outputs, NPN, overload and short-circuit protected
Supplyfrom external auxiliary voltage UAUX
Current1 A per output
Voltage≥ (UAUX - 0.5 V)
Programming instructions
ProfileS-B.A.2
IO codeB
ID codeA
ID1 code7
ID2 code2
Data bits (function via AS-Interface) input output
D0 - OUT1
D1 - OUT2
D2 IN3 -
D3 IN4 -
Parameter bits (programmable via AS-i)function
P0not used
P1not used
P2not used
P3not used
Ambient conditions
Ambient temperature-25 ... 60 В°C (-13 ... 140 В°F)
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Mechanical specifications
Protection degreeIP67 according to EN 60529
ConnectionCable piercing method
flat cable yellow/flat cable black
inputs/outputs: M12 round connector
Material
HousingPBT
Mass100 g
MountingMounting base


Назад в раздел