AS-Interface sensor module | VBA-4E-G2-ZA0

Артикул: VBA-4E-G2-ZA0
Наименование: AS-Interface sensor module | VBA-4E-G2-ZA0
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@quad-industry.com
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@quad-industry.com

  • AS-Interface certificate
  • Protection degree IP67
  • A/B slave with extended addressing possibility for up to 62 slaves
  • Addressing jack
  • Flat cable connection with cable piercing technique, variable flat cable guide
  • Communication monitoring
  • Inputs for 2-, 3-, and 4-wire sensors
  • Supply for inputs from AS-Interface
  • Ground connection (FE) possible
  • Function display for bus and inputs
  • Detection of overload on sensor supply

Datasheet as PDF in following languages:


Technical Data: VBA-4E-G2-ZA0

Product Description
G2 flat module
4 inputs (NPN)
General specifications
Slave typeA/B slave
AS-Interface specificationV2.1
Required master specification≥ V2.0
UL File NumberE87056
Indicators/operating means
LED FAULTerror display; LED red
red: communication error or address is 0
red flashing: overload of sensor supply
LED PWRAS-Interface voltage; LED green
LED INswitching state (input); 4 LED yellow
Electrical specifications
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 40 mA (without sensors) / max. 240 mA
Protection classIII
Input
Number/Type4 inputs for 2- or 3-wire sensors (NPN), DC
alternative 2 inputs for 4-wire sensors (NPN), DC
Supplyfrom AS-Interface
Voltage21 ... 31 V
Current loading capacity≤ 200 mA (TB ≤ 40 В°C),
≤ 150 mA (TB ≤ 60 В°C), overload-proof and short-circuit protected
Input current≤ 8 mA (limited internally)
Switching pointaccording to DIN EN 61131-2 (Type 2)
0 (unattenuated)≤ 2 mA
1 (attenuated)≥ 4 mA
Programming instructions
ProfileS-0.A.2
IO code0
ID codeA
ID1 code7
ID2 code2
Data bits (function via AS-Interface) input output
D0 IN1 -
D1 IN2 -
D2 IN3 -
D3 IN4 -
Parameter bits (programmable via AS-i)function
P0not used
P1not used
P2not used
P3not used
Compliance with standards and directives
Directive conformity
EMC Directive 2004/108/ECEN 50295:1999
Standard conformity
Noise immunityEN 61000-6-2:2005 , EN 50295:1999 , EN 61326-1:2006 , IEC 62026-2:2008
Emitted interferenceEN 50295:1999
AS-InterfaceEN 50295:1999
InputEN 61131-2
Protection degreeEN 60529
Ambient conditions
Ambient temperature-25 ... 60 В°C (-13 ... 140 В°F)
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Mechanical specifications
Protection degreeIP67 according to EN 60529
Connectioncable piercing method
flat cable yellow
inputs: M12 round connector
Material
HousingPBT
Mass100 g
MountingMounting base


Назад в раздел