  • A/B slave with extended addressing possibility for up to 62 slaves
  • Housing with removable and color coded terminals
  • Communication monitoring
  • Inputs for 2- and 3-wire sensors
  • Addressing jack
  • Power supply of outputs from the external auxiliary voltage
  • Supply of inputs external or from the module, as required
  • Function display for bus, ext. auxiliary voltage, inputs and outputs

Datasheet as PDF in following languages:


Technical Data: VBA-4E3A-KE-ZE/E2

Product Description
KE switch cabinet module
4 inputs and 3 outputs
General specifications
Slave typeA/B slave
AS-Interface specificationV2.1
Required master specification≥ V2.1
UL File NumberE87056
Functional safety related parameters
MTTFd150 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Indicators/operating means
LED FAULTFault display; Red LED
red: Communication fault or address is 0
red, flashing: Overload, internal input supply or outputs
LED INTInternal input supply active; LED green
LED PWRAS-Interface voltage; LED green
LED AUXext. auxiliary voltage UAUX ; LED green
LED INswitching state (input); 4 LED yellow
LED OUTSwitching state (output); 3 LED yellow
Electrical specifications
Auxiliary voltage (input)12 ... 30 V DC PELV
Auxiliary voltage (output)20 ... 30 V DC PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 35 mA (without sensors) / max. 190 mA
Protection classIII
Surge protectionUEXT, UAUX, Ue: Over voltage category III, safe isolated power supplies (PELV)
Input
Number/Type4 inputs for 2- or 3-wire sensors (PNP), DC
Supplyfrom AS-Interface (switch position INT, basic setting) or external UEXT (switch position EXT)
Voltage21 ... 31 V DC (INT)
Current loading capacity≤ 150 mA, overload- and short-circuit protected (INT)
Input current≤ 8 mA (limited internally)
Switching pointaccording to DIN EN 61131-2 (Type 2)
0 (unattenuated)≤ 2 mA
1 (attenuated)≥ 4 mA
Signal delay< 2 ms (input/AS-Interface)
Signal frequency≤ 250 Hz
Output
Number/Type3 electronic outputs, PNP, overload and short-circuit proof
Supplyfrom external auxiliary voltage UAUX
CurrentO1 max. 3 A, O2/O3 max. 1.5 A, total 6 A (TB ≤ 40 В°C)
O1 max. 2 A, O2/O3 max. 1 A, total 4 A (TB ≤ 60 В°C)
Voltage≥ (UAUX - 0.5 V)
Usage categoryDC-13
Programming instructions
ProfileS-7.A.0
IO code7
ID codeA
ID1 code7
ID2 code0
Data bits (function via AS-Interface) input output
D0 IN1 O1
D1 IN2 O2
D2 IN3 O3
D3 IN4 -
Parameter bits (programmable via AS-i)function
P0not used
P1not used
P2not used
P3not used
Compliance with standards and directives
Directive conformity
EMC Directive 2004/108/ECEN 61000-6-2:2005, EN 61000-6-4:2007, EN 50295:1999
Standard conformity
Noise immunityEN 61000-6-2:2005
Emitted interferenceEN 61000-6-4:2007
AS-InterfaceEN 50295:1999
InputEN 61131-2:2004
Protection degreeEN 60529:2000
Ambient conditions
Ambient temperature-25 ... 60 В°C (-13 ... 140 В°F)
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Relative humidity90 % , noncondensing
Pollution Degree2
Mechanical specifications
Protection degreeIP20
Connectionremovable terminals
rated connection capacity:
rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2
for multiple-wire connection with two wires of equal cross-section:
flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2
Material
HousingPA 66-FR
Mass150 g
MountingDIN mounting rail