AS-Interface actuator module | VAA-4A-G2-E2

Артикул: VAA-4A-G2-E2
Наименование: AS-Interface actuator module | VAA-4A-G2-E2
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@quad-industry.com
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@quad-industry.com

  • AS-Interface certificate
  • Protection degree IP67
  • Addressing jack
  • Flat cable connection with cable piercing technique, variable flat cable guide
  • Communication monitoring, turn-off
  • Power supply of outputs from the external auxiliary voltage
  • Ground connection (PE) possible
  • Function display for bus, external auxiliary voltage and outputs

Datasheet as PDF in following languages:


Technical Data: VAA-4A-G2-E2

Product Description
G2 flat module
4 electronic outputs (PNP)
General specifications
Slave typeStandard slave
AS-Interface specificationV2.1
Required master specification≥ V2.0
UL File NumberE87056
Indicators/operating means
LED FAULTcommunication error / address is 0; LED red
LED PWRAS-Interface voltage; LED green
LED AUXext. auxiliary voltage UAUX ; LED green
LED OUTSwitching state (output); 4 LED yellow
Electrical specifications
Auxiliary voltage (output)24 V DC ± 15 % PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 30 mA
Protection classIII
Output
Number/Type4 electronic outputs, PNP
Supplyfrom external auxiliary voltage UAUX
Current1.5 A per output, 4 A total
Voltage≥ (UAUX - 0.5 V)
Programming instructions
ProfileS-8.F
IO code8
ID codeF
Data bits (function via AS-Interface) input output
D0 - OUT1
D1 - OUT2
D2 - OUT3
D3 - OUT4
Parameter bits (programmable via AS-i)function
P0communication monitoring
P0 = 1 (basic setting), monitoring = ON, i.e. if communication fails, the outputs are de-energised
P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition
P1not used
P2not used
P3not used
Compliance with standards and directives
Directive conformityobserve notices on the certificate of conformity.
Standard conformity
Noise immunityEN 61000-6-2:2001
Emitted interferenceEN 61000-6-4:2001
AS-InterfaceEN 50295:1999
Protection degreeEN 60529
Ambient conditions
Ambient temperature-25 ... 60 В°C (-13 ... 140 В°F)
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Mechanical specifications
Protection degreeIP67
ConnectionCable piercing method
flat cable yellow/flat cable black
inputs/outputs: M12 round connector
Mass100 g
MountingMounting base