AS-Interface power supply | VAN-115/230AC-K24

Артикул: VAN-115/230AC-K24
Наименование: AS-Interface power supply | VAN-115/230AC-K24
Производитель: Pepperl-Fuchs


Not available for purchase, If you need assistance please contact us sales@quad-industry.com
Оборудование снято с производства, для уточнения замены свяжитесь с нами sales@quad-industry.com

  • 8 A output load
  • 115 V AC / 230 V AC switchable
  • SELV
  • LED operating display
  • AS-Interface data decoupling
  • Power factor correction
  • Electronic overload protection and display

Datasheet as PDF in following languages:


Technical Data: VAN-115/230AC-K24

Product Description
AS-Interface power supply
General specifications
UL File NumberE223176
Functional safety related parameters
MTTFd40 a
Mission Time (TM)10 a
Diagnostic Coverage (DC)0 %
Indicators/operating means
Power selection switchchangeover switch for 115 V AC/230 V AC
LED OverloadRed LED, flashing
LED PWRLED green
Electrical specifications
Fusing6.3 AT
Capacity factorapprox. 0.62 (Depending on input voltage)
Rated operating voltageNominal: 115 V AC/230 V AC (selectable on front)
Permitted: 90 to 132 V AC/190 to 265 V AC
Rated operating current4.0 A (115 V switch position)
1.9 A (230 V switch position)
Supply frequency47 ... 63 Hz
Efficiencyapprox. 87 %
Output
Current limitapprox. 8.5 A
Current8 A
Voltage29.5 ... 31.6 V DC
Standard conformity
Electromagnetic compatibilityEN 55011, EN 50082-1, EN 61000-6-2
AS-InterfaceEN 50295
StandardsHarmonic waves: EN 61000-3-2 Class A
Interference suppression: EN 55022, EN 55011 Class B
Electrostatic discharge (ESD): IEC 61000-4-2 (8 kV contact discharge, 15 kV air discharge)
Electromagnetic fields: IEC 61000-4-3 (EN 61000-4-3)
Burst: IEC 61000-4-4 (4 kV input, 2 kV output/capacitively coupled)
Surge: IEC 61000-4-5 (4 kV asymmetrical, 4 kV symmetrical)
Conducted interference: IEC 61000-4-6 (10 V, 150 kHz to 80 MHz)
Ambient conditions
Ambient temperature-10 ... 55 В°C (14 ... 131 В°F) with free convection
Storage temperature-25 ... 85 В°C (-13 ... 185 В°F)
Mechanical specifications
Protection degreeIP20
Protection classI, Protective conductor connection necessary
ConnectionConnection terminals, max. conductor cross-section
0.5  to  2.5 mm2
Stripping length 5  to  6 mm
Massapprox. 1200 g
MountingDIN mounting rail


Назад в раздел